There is no single oxygen limit for natural gas pipelines. Each pipeline sets its own maximum in its tariff or gas quality specification, and published values range from 10 ppm (0.001 % by volume) on the strictest systems to 0.2 % by volume on several interstate pipelines, and an older industry compilation lists a few higher values. The limit that applies to your gas is the one written for your receipt point or contract, so read that document before you pick an analyzer range or an alarm setpoint.
The published limits below come from pipeline tariffs, utility gas rules and an industry compilation. They show how wide the range is, and they are examples only. Tariffs change, so confirm the current text with the pipeline before you design to any of these numbers.
| Pipeline or utility | Published oxygen limit | In ppm by volume | Source type |
|---|---|---|---|
| Southern Star Central Gas Pipeline, Line Segments 315, 340 and 385 | 10 ppm | 10 | FERC tariff text accepted in 2018 |
| Colorado Interstate Gas (2009 compilation) | 0.001 % | 10 | AGA Report 4A, 2009 compilation |
| Northwest Pipeline, receipt points connected to the La Plata Facilities | 0.1 % | 1,000 | FERC tariff |
| Questar Pipeline (2009 compilation) | 0.10 % | 1,000 | AGA Report 4A, 2009 compilation |
| PG&E (California utility), Gas Rule 21 | 0.1 % | 1,000 | Utility tariff rule |
| Northwest Pipeline, other receipt points | 0.2 % | 2,000 | FERC tariff |
| Southern Star Central Gas Pipeline, other receipts | 0.2 % | 2,000 | FERC tariff text accepted in 2018 |
| SoCalGas (California utility), Rule 30 | 0.2 % | 2,000 | Utility fact sheet |
| Florida Gas Transmission (2009 compilation) | 0.25 % | 2,500 | AGA Report 4A, 2009 compilation |
| Gas Transmission Northwest (2009 compilation) | 0.40 % | 4,000 | AGA Report 4A, 2009 compilation |
The rows marked 2009 compilation are taken from a table in a SoCalGas fact sheet that cites the American Gas Association's 2009 Report 4A. Those values are from 2009, and current tariffs may differ. The Southern Star rows reflect tariff text FERC accepted in 2018, and a later Southern Star filing proposed changes, so check the current tariff. Each source is linked at the end of this article.
Pipeline oxygen limits differ because each operator weighs its own corrosion risk, its downstream delivery obligations and the gas it already receives. A system that delivers into pipelines with tighter limits has to hold its own gas to a tighter number, or it cannot hand the gas on.
A 2021 Southern Star proposal to its customers shows that reasoning. That proposal, which was not adopted and which Southern Star later replaced, would have lowered the general oxygen limit from 0.2 % to 10 ppm to reduce internal pitting and crevice corrosion, noted that oxygen makes CO₂ and H₂S corrosion more severe, and cited consistent deliveries to pipelines with more stringent limits. Southern Star's later customer update replaced the systemwide 10 ppm idea with a plan to keep the 0.2 % limit and add a 10 ppm oxygen option for gas carrying more CO₂. A gas processing paper from Trimeric Corporation also reports that oxygen limits in new contracts have trended downward over recent years.
Some tariffs also cap oxygen inside a combined limit. Northwest Pipeline, for example, caps total inerts, including oxygen, at 3 % by volume, and the SoCalGas fact sheet lists a 4 % total inerts limit.
The limit for your interconnect is in the quality section of the receiving pipeline's tariff, often in the General Terms and Conditions, or in your gas purchase or gathering agreement if that agreement sets its own number. Check the following points before you rely on a number:
Some tariffs leave room for operator discretion. Southern Star's tariff, for example, states that the pipeline may accept gas above 10 ppm on its restricted segments based on operational and engineering considerations, including its ability to blend that gas and still meet downstream specifications.
Air is about 21 % oxygen, so each oxygen limit corresponds to a small amount of air leaking into gas that held no oxygen before the leak. The arithmetic shows why a 10 ppm system leaves almost no room for air ingress.
| Oxygen limit | In ppm | Equivalent air in the gas |
|---|---|---|
| 10 ppm (0.001 %) | 10 | About 48 ppm of air, roughly 1 part in 21,000 |
| 0.1 % | 1,000 | About 0.48 % air |
| 0.2 % | 2,000 | About 0.95 % air |
| 0.25 % | 2,500 | About 1.2 % air |
| 0.4 % | 4,000 | About 1.9 % air |
This table is arithmetic only, not a field measurement. The table assumes that air is about 21 % oxygen and that the gas contained no oxygen before air entered.
For the sources of that air, from tank hatches to compressor packing, see oxygen in natural gas: sources, limits and where to measure.
Choose a range that puts your limit well inside the scale, with enough headroom above the limit to see an upset rather than a pegged signal. OxyScout offers five ranges, and the table below matches them to the limit bands in this article.
| Your oxygen limit | OxyScout range to consider | Why |
|---|---|---|
| 10 ppm | Ultra-Trace, 0–50 ppm* | The limit sits low in the scale, and the range leaves headroom to watch a rise above the limit. |
| Up to about 0.05 % (500 ppm) | Trace, 0–1000 ppm* | The limit sits mid-scale, with room above it for upsets. |
| 0.1 % to 0.4 % | Percent, 0–1 %vol* | The limit sits inside the scale, and the range can follow a larger air leak without saturating. |
| Upset tracking above 1 % | Percent, 0–10 %vol* or 0–21 %vol* | These ranges follow large air ingress events up to air itself. |
On the Ultra-Trace range, the limit of detection is ≤0.5 ppm* and accuracy is ±2 ppm or ±5 % of reading, whichever is greater*. On the Trace range the limit of detection is 50 ppm*, and on the Percent ranges it is 0.01 %vol* (0–1 %) and 0.1 %vol* (0–10 % and 0–21 %). Accuracy is ±0.5 % of full scale* on the 0–1 %vol Percent range, and ±5 % of full scale* on the Trace range and the 0–10 % and 0–21 %vol ranges. Typical response is under 10 seconds*.
On the 0–1 %vol range, ±0.5 % of full scale equals ±0.005 %vol*, which is small relative to a 0.1 % limit and smaller still against limits of 0.2 to 0.4 %.
*Based on controlled lab conditions.
See the full specifications on the optical oxygen analyzer page.
At the fence line, a continuous analyzer monitors oxygen against your pipeline limit, so operators see a rising trend before gas reaches the receiving pipeline's own measurement. OxyScout sends its reading over 4–20 mA and RS-485 Modbus RTU, so you can set your own alarm point below the limit in your RTU, PLC or SCADA. The receiving pipeline's measurement and its tariff terms still govern acceptance of the gas.
A single fence-line reading shows the cumulative oxygen from every upstream source. To find where the air enters, add readings upstream at gathering lines, compressor stations and vapor recovery units. The custody transfer page shows where the analyzer mounts at the interconnect.
OxyScout is engineered for Class 1 Division 2 (Zone 2) hazardous areas and has no H₂S or CO₂ cross-sensitivity. The analyzer is priced comparably to electrochemical analyzers, and because there are no cells to replace, its total cost of ownership over 2–3 years is much lower. To review your limit, range and sample point with an engineer, book a quote meeting.
No single number applies to every pipeline. Interstate pipelines publish their gas quality terms, including oxygen, in their own FERC gas tariffs, so the limit is set pipeline by pipeline and sometimes segment by segment.
Ten ppm by volume is 0.001 % by volume. One percent by volume is 10,000 ppm.
Several of the interstate tariffs in this article use 0.2 % by volume, and some systems use 0.1 % or 10 ppm. Confirm the limit in the tariff or agreement for your receipt point.
Some tariffs allow the pipeline to accept off-spec gas at its discretion, for example when it can blend the gas and still meet downstream specifications. That acceptance is the pipeline's decision and should not be assumed.
Utilities and pipelines set their own limits for renewable natural gas, for example 0.2 % in SoCalGas Rule 30 and 0.1 % in PG&E Gas Rule 21. See oxygen in biogas and RNG.
The Ultra-Trace range places a 10 ppm limit low in the scale and leaves headroom to see a rise above it.